64 AGZ 030A through 065A IOM 686
Menu Structure (general description)
The information stored in the MicroTech controller can be accessed through the keypad using a tree-
like structure. This tree structure is divided into Categories, Menus and Menu Items. There are three
Categories which make up the tree structure: STATUS, CONTROL, and ALARM. Each category is
divided into Menus and each Menu into Menu Items. The three categories are described below:
Status category- Menus and menu items in this category provide information on the MicroTech
and unit operating conditions. The entries under each menu item in this category provide
information only and are not changeable through the MicroTech keypad. Menus 1 through 12 are
Status Menus.
Control category- Menus and menu items in this category provide for the input of all the unit
control parameters. These include cooling and heating control, compressor control and condenser
fan control parameters as well as time schedules and alarm limits. The entries under these menu
items are changeable through the MicroTech keypad. Menu Items 13 through 23 are Control
Menus.
Alarm category - Menu and menu items in this category provide information regarding current
and previous alarm conditions. Menus 23 through 27 are Alarm Menus.
Display Format
The information stored in the MicroTech controller tree structure can be viewed (one menu and menu
item at a time) through a two line by sixteen character LCD display. The current MENU is shown on
the top line and the current MENU item is shown on the bottom line of the display.
MicroTech Menu Structure
1. Status category- Where ore than one menu item entry is listed under a menu item, the list includes
all the entries which can appear in the display for the particular item. The entry that shows in the
display depends on the operating status of the unit.
2. Control category - Where more than one menu item entry is listed under a menu item, the list
includes all the choices from which the user can select. The selected entry appears in the display.
3. Alarm category-The entries listed include all the possible alarm messages. The display will show
the current and previous alarm conditions for each circuit.
Password Information
When changing any menu item entry, the user is prompted to enter the access password. The change
will not be allowed until the correct password is entered. The password for ALR and WHR units is
always the successive pressing of the following “ACTION” group keys:
“ENTER” “ENTER” “ENTER” “ENTER
Once this has been done, the user can make changes to the menu item entries. After entering the correct
password, the controller will allow a 5 minute time period during which the operator may make any
necessary setpoint adjustments. Any keypad activity will reset the timer for the full 5 minutes so the
password only needs to be entered once per session. After 5 minutes of inactivity, the password access
time will expire providing protection against unauthorized users.

Table of Contents

Other manuals for McQuay AGZ 065A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay AGZ 065A and is the answer not in the manual?

McQuay AGZ 065A Specifications

General IconGeneral
BrandMcQuay
ModelAGZ 065A
CategoryChiller
LanguageEnglish

Related product manuals