General Data - Heat pump R410A Inverter
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
54
M5ACV075CR
Btu/h
70000
W
20515
Btu/h 75000
W 21980
COOLING W 9050
HEATING W 7900
COOLING A 16.6
HEATING A 15.4
V/Ph/Hz
380-415 / 3 / 50
R410A
ELECTRONIC EXPANSION VALVE
HEIGHT mm/in
1460 / 57.5
WIDTH mm/in
1150 / 45.3
DEPTH mm/in
550 / 21.7
HEIGHT mm/in
1626 / 64.0
WIDTH mm/in
1309 / 51.5
DEPTH mm/in
656 / 25.8
kg/lb
200 / 440
dBA
65
COOLING
l/s / m
3
/hr
0.95 ( 3.4 )
HEATING
l/s / m
3
/hr
1.03 ( 3.7 )
PROPELLER / DIRECT
2
HORIZONTAL MULTISTAGE END-SUCTION
MAX. WATER OPER. PRESSURE kPa / psi 1000 / 145
COOLING
l/s / m
3
/hr
0.9 ( 3.4 )
HEATING
l/s / m
3
/hr
1.0 ( 3.7 )
INSTALLATION PIPE CONNECITON mm/in
25.4 / 1
COOLING m
22.4
HEATING m
20.5
NOT APPLICABLE
L / ft
3
NOT APPLICABLE
SCROLL
0 - 75000
kg/lb 4.8
TANK
PIPING
TYPE
COMPRESSOR
HEAD
MATERIAL
REFRIGERANT
CHARGING MASS
STAGE OF CAPACITY CONTROL (Btu/h)
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
CONTROL
CAPACITY/VOLUME
UNIT DIMENSION
PACKING DIMENSION
UNIT WEIGHT
PUMP
TYPE
WATER FLOW RATE
HYDRAULIC KIT
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
EVAPORATOR
CONDENSER FAN
SOUND PRESSURE LEVEL
NOMINAL WATER FLOW