Model : M5ACV 210CR - Heating
69
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 46.14 18.00 36.8 46.75 18.01 36.8 54.77 18.12 37.0 10.75 185 1363 2.5
40 45.01 19.54 40.0 45.84 19.55 40.0 53.59 19.64 40.2 10.50 192 1350 2.4
45 43.87 21.30 43.6 44.88 21.31 43.6 52.51 21.43 43.8 10.30 197 1340 2.4
50 42.07 23.24 47.5 43.16 23.27 47.6 51.19 23.50 48.0 10.12 202 1330 2.4
55 39.76 25.42 52.0 40.93 25.47 52.1 49.62 25.82 52.8 10.01 205 1324 2.4
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 59.69 18.30 37.4 64.26 18.48 37.8 67.08 18.72 38.3 10.75 185 1363 2.5
40 58.48 19.79 40.4 62.73 19.93 40.8 65.83 20.12 41.1 10.50 192 1350 2.4
45 57.44 21.59 44.1 61.55 21.80 44.6 64.84 21.93 44.8 10.30 197 1340 2.4
50 56.40 23.76 48.6 60.48 23.87 48.8 64.22 24.06 49.2 10.12 202 1330 2.4
55 55.26 26.12 53.4 59.82 26.37 53.9 63.71 26.64 54.5 10.01 205 1324 2.4
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A m3/hr kPa W A
35 72.36 19.21 39.3 83.37 20.82 42.6 10.75 185 1363 2.5
40 70.88 20.50 41.9 81.98 22.03 45.0 10.50 192 1350 2.4
45 69.72 24.43 49.9 81.04 23.97 49.0 10.30 197 1340 2.4
50 69.72 24.43 49.9 80.82 26.10 53.4 10.12 202 1330 2.4
55 69.00 27.16 55.5 29.14 29.14 59.6 10.01 205 1324 2.4
LEAVING WATER TEMP (°C