Installation & Maintenance Data IM 934-2
Group: PTAC
Part Number: 668966802
Date: October 2009
Applied Packaged Terminal Air Conditioner and Heat Pump
Model PDAA & PDHA Dual Motor Angled Top Unit - 16" x 42" with R-410A Refrigerant

Table of Contents

Questions and Answers

  • B
    Brandy CurryAug 17, 2025
    How to troubleshoot McQuay PDAA Air Conditioner blowers that won't operate on cool?
    • Z
      Zachary RobinsonAug 17, 2025
      If the blowers of your McQuay Air Conditioner aren't working in cool mode, here's what to check: * **No power:** Verify the power supply by checking fuses and circuit breakers, and ensure the unit is powered on. Blown fuses often indicate a circuit overload, short circuit, or a ground condition. Also, confirm that the voltage supply is within 10% of the rating on the unit's data plate. * **Faulty push-button switch:** If the power supply is okay, the push-button switch might be defective and needs replacement. * **Loose connections:** Check for and tighten any loose connections at the push-button switch.
  • J
    Jamie EwingAug 22, 2025
    Why does my McQuay PDAA Air Conditioner compressor start and then stop quickly?
    • J
      Jacob PetersonAug 22, 2025
      If the compressor in your McQuay Air Conditioner starts but stops after a short period, it might be due to the overload device activating because of an overloaded compressor motor. Check the voltage supply, clean the condenser (inside and out), and ensure there's no recirculation of condenser air at the outside face of the condenser. If air splitters are missing, install them. Also, check the compressor for a short circuit. If the compressor is defective, ship the cooling chassis to the nearest McQuay authorized warranty station.
  • L
    Laurie SanchezAug 30, 2025
    What causes McQuay PDAA Air Conditioner compressor to run but blowers not to run?
    • L
      Laura HintonAug 30, 2025
      If the compressor in your McQuay Air Conditioner starts and runs in cool mode, but the blowers do not operate, check the following: * **Faulty switch:** The push-button switch might be faulty and need replacement. * **Blower motor:** The blower motor might be open circuited and require replacement. * **Blower obstruction:** The blower might be rubbing against its housing, requiring adjustment of the blower motor or blower wheel position. * **Seized bearings:** The blower motor bearings may be seized, necessitating motor replacement. * **Loose connection:** There may be a loose connection at the push-button switch that needs tightening.
  • C
    Carlos ChanSep 2, 2025
    Why McQuay Air Conditioner blowers don’t operate on heat?
    • M
      Michael BartlettSep 2, 2025
      If the blowers on your McQuay Air Conditioner aren't working in heat mode, consider these possible causes: * **No power:** Ensure the unit has power by checking the power supply line, fuses, and circuit breakers. * **Heat is off:** If the equipment has a heat fan lockout, open the heat valve or turn on the heating system. * **Faulty switch:** A faulty push-button switch may need replacement. * **Loose connections:** Tighten any loose connections at the push-button switch. * **Thermostat setting:** The thermostat might be set too low; adjust it to a warmer setting.
  • K
    Kimberly GaySep 7, 2025
    What causes "sweating" in a McQuay Air Conditioner?
    • L
      Leah MasseySep 8, 2025
      If your McQuay Air Conditioner is experiencing "sweating," here are some possible causes: * **Condensate drain:** The condensate drain from the evaporator to the condenser might be plugged. Remove any obstructions to water flow. * **Insulating seals:** Damaged insulating seals on the equipment may need adjustment or replacement. * **Evaporator blower motor:** The evaporator blower motor might not be running at the correct speed. Check the voltage and replace the motor if necessary. * **Blower position:** The evaporator blower may be incorrectly positioned. Ensure it is tightened properly.
  • T
    Tim LivingstonSep 10, 2025
    Why is my McQuay PDAA Air Conditioner providing too much cooling?
    • L
      Lauren GonzalesSep 10, 2025
      If your McQuay Air Conditioner is providing too much cooling, it could be due to: * **Thermostat setting:** The thermostat might be set too low. Adjust the thermostat to a warmer setting. * **Defective thermostat:** The thermostat itself might be defective and need replacement.
  • K
    Kathryn LongSep 13, 2025
    What to do if McQuay Air Conditioner gives electrical shock?
    • N
      Nicole JimenezSep 13, 2025
      If your McQuay Air Conditioner is giving an electrical shock, it indicates a grounded electrical circuit. You should eliminate the ground.
  • L
    Linda JohnsonNov 18, 2025
    What to do if McQuay PDAA blowers work but compressor doesn't start?
    • T
      turnermonicaNov 18, 2025
      If your McQuay Air Conditioner's blowers are running but the compressor isn't starting, consider these potential causes and solutions: 1. **Thermostat setting:** Ensure the thermostat isn't set too high. Adjust it to a cooler setting. 2. **Heat valve:** Check if the heat valve is open, causing heat to be on. If so, close the heat valve. 3. **Low voltage:** Low voltage can prevent the compressor from starting. Check the power supply, fuses, and circuit breakers. 4. **Touchpad switch:** A faulty touchpad switch may be the culprit. Replace it if necessary. 5. **Loose connections:** Tighten any loose connections at the touchpad switch or compressor terminals. 6. **Wiring issues:** Defective wiring to the thermostat or compressor terminals should be replaced. 7. **Compressor overload:**...
  • H
    heather89Nov 24, 2025
    Why does my McQuay PDAA Air Conditioner compressor stop occasionally on overload?
    • H
      Harold HowardNov 24, 2025
      If your McQuay Air Conditioner's compressor starts and runs but occasionally stops due to the overload device, here are possible reasons: * **Low voltage:** Low voltage, caused by overloaded circuits in the building or the local power system, might be the issue. This can happen at specific times of the day or on hot days. Consider running a separate electrical line or consulting your local power company. * **High voltage:** High voltage, due to fluctuations in the local power system, typically during low load periods, can also cause this. Consult your local power company. * **Partial short circuit:** A partial short circuit in the compressor motor might seem fine under normal conditions, but increased condensing air temperature can trigger a short. If confirmed, ship the cooling cha...
  • F
    fbrownNov 26, 2025
    How to fix a noisy McQuay PDAA?
    • C
      Charles YoungNov 27, 2025
      If your McQuay Air Conditioner is making excessive noise, consider the following potential causes: * **Blower issues:** Check if the blower is rubbing against the enclosure and adjust its position. Also, dry blower motor bearings can cause noise, requiring motor replacement. Ensure blower hold-down nuts are tightened. * **Refrigerant issues:** Refrigerant absorbed in the compressor oil after a long shutdown can cause temporary noise; this should disappear after the equipment runs for a while. * **Installation:** Improper installation may lead to noise. Make necessary adjustments to the components. * **Damper solenoid:** A humming damper solenoid might need adjustment and lubrication with silicone oil or grease. * **Loose components:** Tighten any loose terminal box covers, elect...

Summary

Safety Information and Unit Inspection

General Safety Precautions

Follow all safety codes, wear protective gear, and be aware of DANGER, WARNING, CAUTION meanings.

Critical Safety Warnings

Covers hazardous voltage, electrical shock, and property damage warnings.

Subbase Installation

Condensate Drain Kit Installation

Wall Sleeve Installation

Recessed Louver Wall Sleeve Installation

Basic Wall Sleeve Installation Procedures

Basic Wall Sleeve Installation: Frame and Brick Types

Basic Wall Sleeve Installation: Panel Wall Types

Wall Sleeve to Subbase Attachment

Basic Wall Sleeve Installation: Thick Wall Types

Thick Wall Installation with Hydronic Subbase

Louver and Chassis Installation

Chassis Installation Procedure

Steps for properly installing the unit chassis into the wall sleeve.

Controls: Standard Digital Touchpad

Control Overview and Interface

Details the touchpad control, its application, inputs/outputs, and user interface.

Standard Touchpad Operation

Explains operation modes like memory recall, on/off, fan control, and remote thermostat mode.

Remote Thermostat and System Modes

Covers system selection, lockout features, and various operational modes.

Heat Mode and Set Up Configuration

Describes heat mode features like Hot Start and the Set Up mode.

Operational Safeguards and Limits

Covers sensor readings, failure codes, protective features, and temperature limits.

Controls: Premium Digital Touchpad

Premium Touchpad Operation

Operating instructions for the premium programmable digital touchpad control.

Automatic Changeover Feature

Describes the automatic changeover from cooling to heating and vice versa.

Clock and Configuration Settings

Procedure for setting the clock and configuring temperature limits and sensor readings.

Thermostat Programming

Details on programming daily schedules with time periods and temperatures.

Thermostat Options

Remote Thermostat Installation

Wiring Diagrams

Premium Digital Control Wiring

Wiring diagram for the premium programmable digital control.

Standard Digital Control Wiring

Wiring diagram for the standard non-programmable digital control.

Digital Control with Standby Power

Wiring diagram for digital control board with standby power.

Digital Control Without Standby Power

Wiring diagram for digital control board without standby power.

Scheduled Maintenance

Routine Maintenance Tasks

Covers air filter cleaning, chassis checkup, coil cleaning, and component checks.

Troubleshooting Codes

Control Board Fault Codes

Lists fault codes, descriptions, and causes for control board errors.

Troubleshooting Common Issues

McQuay PDAA Specifications

General IconGeneral
BrandMcQuay
ModelPDAA
CategoryAir Conditioner