DC32D GENSET CONTROLLER USER MANUAL
19
to normal, the alarm of over speed is reported. "ALARM" lights flicker, Generator
stops running, and displays " Over Speed " on the LCD screen.
Under Speed Alarm
When the controller detects that the engine speed is under than Under speed
alarm”, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of under speed is reported. "ALARM" lights flicker,
Generator stops running, and displays " Under Speed " on the LCD screen.
Low Oil Pressure Switch Alarm
When the controller detects that the Low Oil Pressure alarm switch input is valid to
the ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Low Oil Pressure Switch is reported. "ALARM" lights
flicker, Generator stops running, and displays " Low OP switch" on the LCD screen.
High Temperature Sensor Alarm
When the controller detects that the engine Temperature is higher than High
temperature alarm”, Then start alarm delay and the duration (Normal alarm delay)
have not returned to normal, the alarm of High Temperature is reported. "ALARM"
lights flicker, Generator stops running, and displays " High WT sensor " on the LCD
screen.
High Temperature Switch Alarm
When the controller detects that the High temperature alarm switch input is valid to
the ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of High Temperature Switch is reported. "ALARM"
lights flicker, Generator stops running, and displays "High WT switch" on the LCD
screen.
Temperature Sensor Opened Alarm
When the safety delay is over, the controller detects that the Temperature Sensor is
disconnected, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of the Temperature Sensor opened is reported.
"ALARM" lights flicker, Generator stops running, and displays " WT sensor open "
on the LCD screen.
Fuel Level Sensor Opened Alarm
When the safety delay is over, the controller detects that the Fuel Level Sensor is
disconnected, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of the Fuel Level Sensor opened is reported. "ALARM"
lights flicker, Generator stops running, and displays " FL sensor open " on the LCD
screen.
Low Fuel Level Switch Alarm
When the controller detects that the Low fuel level alarm switch input is valid to the
ground, Then start alarm delay and the duration (Normal alarm delay) have not
returned to normal, the alarm of Low fuel level switch is reported. "ALARM" lights
flicker, Generator stops running, and displays " Low FL switch " on the LCD screen.
External Instant Alarm
When the controller detects that the External instant alarm input input is valid to the
ground, Then start alarm delay and the duration (Normal alarm delay) have not