DC32D GENSET CONTROLLER USER MANUAL
26
delay is completed, and the output is invalid after
high-speed heat dissipation.
10.
Fan Control: used to control radiator electrical
fan. there is output when the preset temperature is
higher than " Temperature for Fan open" and no
output when the preset temperature is lower than
"Temperature for Fan close".
11. E.S.T. hold: shutdown output, it is used for gens
with stop solenoid. when the setting value of
shutdown delay is over, then it is off.
12.
Rated running: there is output under rated
running.
13. Gens unload:Continuous or pulsed output,
determined by the opening output time.
14.
Mains load:Continuous or pulsed output,
determined by the closing output time.
15. Mains Unload:Continuous or pulsed output,
determined by the opening output time.
16.
Public Unload control:Public unload function,
mains unload and genset unload will output.
17. Preheat mode 2: preheat before crank success.
18.
Preheat mode 3: preheat after safety delay.
19.
Preheat mode 4: preheat till temperature-up end.
20. Preheat mode 5: preheat till temperature-up end,
but no preheat when motor starts.
2
AUX. INPUT
SWITCH 1
Functional
of PIN 6
0-14(1. Remote
start)
0.Disable.
1.Remote start switch input.
2.Low oil pressure alarm switch input.
3.High temperature alarm switch input.
4.Low water level alarm switch input.
5.Low fuel level warning switch input.
6.Low fuel level alarm switch input.
7.External instant warning input.
8.External instant alarm input.
9.High temperature cooling and Stop Input : When
the signal is valid and the generator is in normal
operation, if there is a high temperature alarm, the
controller first after the Cooling time delay after the
temperature is lower than the high temperature alarm
value before stopping; when the signal is invalid, if
there is a high temperature alarm, the controller will
stop directly.
10.Emergency stop.
11.Pump fail alarm switch input-Normally
closed valid.
12.Pump fail warning switch input-Normally
closed valid.
13.Pump fail alarm switch input-Normally open valid.
14.Pump fail warning switch input-Normally
open valid.
3
AUX. INPUT
0-14
0.Disable.