Factory reset to Default settings
Factory default settings
SETUP - change test pass limits, test times and test lead resistance. SETUP is “test group based” as the PASS limit for a Class I insulation test is different to a Class II insulation test.
Factory Default Test Limits
Variant Model
Rpe, Rcont
(Ω)
Rpe, Rcont
(Ω)
for Ext
lead
Rpe, Rcont
(Ω)
for RCD
Class 1
Riso, Rins
(MΩ)
Class 2
Riso, Rins
(MΩ)
Ext lead
Riso, Rins
(MΩ)
Class 1
Iea,
ileak(sub),
ipe, ileak
(mA)
It, I
b
Class 2
iea, I
t
(sub)
(mA)
1xIΔN30
(ms)
5xIΔN30
(ms)
1xIΔN10
(ms)
5xIΔN10
(ms)
PAT120-UK 0.2 0.2 0.2 1 2 1 3.5 0.25 NA NA NA NA
PAT150-UK 0.2 0.2 0.2 1 2 1 3.5 0.25 200 40 200 40
PAT120-DE, PAT120-CH,
PAT120-EU
0.3 0.3 0.3 1 2 1 3.5 0.5 NA NA NA NA
PAT150-DE, PAT150-CH,
PAT150-EU
0.3 0.3 0.3 1 2 1 3.5 0.5 300 NA 300 NA
PAT150-AU 1 1 1 1 1 1 5 1 300 NA 40 NA