18 
 
accelerati
on/ 
decelerati
on) 
P01.05 
Output 
frequency 
Output 
frequency 
-3000.00~3000.00Hz 0.01Hz 0.00 × √ * 
P01.06 
Output 
voltage 
Output 
voltage 
0~480V 1V 0 × √ * 
P01.07 
Output 
current 
Output 
current 
0.0~3Ie 0.1A 0.0 × √ * 
P01.08 
Torque 
current 
Torque 
current 
-300.0~+300.0% 0.1% 0.0% × √ * 
P01.09 
Flux 
current 
Flux current 
0~+100.0% 0.1% 0.0% × √ * 
P01.10 
Output 
torque 
Output 
torque 
-300.0~+300.0% 0.1% 0.0% × √ * 
P01.11 
Motor 
power 
Motor power
0.0~200.0% (relative to the rated 
power of the motor) 
0.1% 0.0% × √ * 
P01.12 
Estimated 
frequency 
of motor 
Estimated 
frequency of 
motor 
-650.00~650.00Hz 0.01 0.00 × × * 
P01.13 
Measured 
frequency 
of motor   
Measured 
frequency of 
motor  
-650.00~650.00Hz 0.01 0.00 × × * 
P01.14 
High level 
of output 
(kWh) 
Output (kWh)
0~65535*10000kWh 
10000kW
h 
0 × √ * 
P01.15 
Low level 
of output 
(kWh) 
Output (kWh) 0~9999kWh  1kWh  0  × √ * 
P01.16 
Bus 
voltage 
Bus voltage 
0~800V 1V 0 × √ * 
P01.18 
State of 
digital 
input 
terminal 
DI terminal 
state 
0~FFH, 0: off; 1: on 
The high-speed pulse reference 
will not be refreshed 
synchronously 
1 00 × √ * 
P01.19 
State of 
digital 
output 
terminal 
DO terminal 
state 
0~FH, 0: open; 1: close 
The high-speed pulse output will 
not be refreshed synchronously 
1 0 × √ * 
P01.29 
Estimated 
temperatu
re of 
motor 
Estimated 
temperature 
of motor 
0~200℃ 1℃ 
0 × √ * 
Group P02: Basic parameters 
P02.00 
Control Control 
0: Vector control without PG 
1 00 √ √ ×