66 
 
 
Please carefully choose the fault alarm function; otherwise, the accident range extension, the human injury 
and the property damage may be caused. 
6.2   Operation exception and solutions 
Table 6-3    Operation exception and solutions 
Symptoms  Conditions  Possible causes  Solutions 
The 
operation 
panel has no 
response. 
An individual key or 
each key has no 
response. 
The locking function of the 
operation panel takes effect. 
In stop or running status, press the M key and 
retain pressure on it, then press the V key 
successively for three times, after that, you can 
unlock it. 
Completely power off the drive and then power 
it up 
The wires of the operation panel 
have poor contact. 
Check the wires and perform the hot plug 
again 
The keys of the operation panel are 
damaged. 
Replace the operation panel or seek for 
service support 
The function 
code can not 
be modified. 
Can not be modified in 
running status 
The function code can not be 
modified in running status. 
Modify it in the stop status 
A portion of function 
code can not be 
modified. 
The function code P00.03 is set as 
1 or 2. 
Set the P00.03 as 0 
The function code is actual 
detection value. 
Actual parameters can not be changed by 
users. 
There is no response 
when MENU/ESC key 
is pressed. 
The locking function of the 
operation panel takes effect or 
others. 
See the solutions to “the operation panel has 
no response” 
Can not enter the 
editing state after 
pressing the 
MENU/ESC key; the 
function code status 
display is 0000. 
User password is set. 
Input the user password correctly 
Seek for service support 
The drive 
stops 
unexpectedly 
during 
In the case that there 
is no stop command, 
the drive stops 
automatically and the 
Fault alarm occurs.  Find out the fault causes and reset the fault 
A single cycle of the simple PLC is 
completed. 
Check the PLC parameter setting 
There is power supply interruption.  Check the power supply