65 
 
Alarm 
code 
Alarm type  Possible alarm causes  Solutions 
AL.oL2 
Motor overload 
The motor overload protection factor 
setting is incorrect. 
Set the overload protection factor of motor correctly. 
The motor is blocked or the sudden 
change of load is too large. 
Check the load 
The universal motor runs at low speed 
for a long time, with heavy load. 
If long-term low-speed running is required, special 
motor should be used. 
The grid voltage is too low.  Check the grid voltage   
V/F curve is improper.  Set V/F curve and torque increase correctly 
AL.EEP 
EEPROM 
read/write  
fault 
The read/write error of the control 
parameters occurs. 
Reset by pressing the STOP/RESET key, seek for 
service support 
AL.SC1 
Abnormal 
serial port 
communication  
The baud rate is set improperly.  Set the baud rate properly. 
Serial port communication error 
Reset by pressing the STOP/RESET key, seek for 
service support 
The fault alarm parameters are set 
improperly. 
Modify the P15.03 and P97.00 settings 
The host device does not work. 
Check if the host device is working and if the wiring is 
correct. 
AL.rLy1 
Abnormal 
contactor  
The grid voltage is too low.  Check the grid voltage 
The contactor is damaged. 
Replace the contactor of the main circuit, seek for 
service support 
The power-up buffer resistance is 
damaged. 
Replace the buffer resistance, seek for service 
support 
The control circuit is damaged.  Seek for service support 
Input phase loss  Check the input R.S.T. wiring 
AL.EGL 
External 
reference 
command lost 
During the frequency main reference or 
the torque command selection analog 
current reference, the analog reference 
signal is disconnected or too low (less 
than 2mA). 
Check the wiring or adjust the input type of the 
reference signal 
AL.24v 
Control board 
24V power 
short circuit   
Short circuit of P24 and terminal COM 
Confirm whether the wiring of P24 and COM is 
correct  
The interface board circuit is damaged. Replace the interface board, seek for service support