Overspeed detection action selection: 
0: Decelerate to stop 
The drive decelerates to stop according to the deceleration time, and the failure of Er.oSP is reported.   
1: Coast to stop 
The drive is subject to coast to stop, and the failure of Er.oSP is reported.   
2: Continue to run 
The drive reports the alarm of AL.oSP and keeps running. 
 
 
 
 
In order to improve the efficiency of the lifting device, at light loads the user wishes the motor to work 
above the rated frequency, the deive automatically calculates the current operating frequency of the 
motor according to the motor power-torque curve. This function is selected by [P61.09]. 
0: Disable 
1: For uplink 
2: For uplink and downlink 
When the drive output frequency exceeds the motor rated frequency, power limits come into play. If the 
power exceeds [P61.10] or [P61.11] setting value, the drive stops accelerating and maintains the current 
speed regardless of whether the acceleration at that time is 0 or not. 
 
 
Power control acceleration and deceleration rates 
0.0~50.00Hz/s2(5.00)
P61.12 
Maximum 
ower limit for downlin
00.0~ 100.0%(75.0%)
P61.11 
Maximum 
ower limit for u
lin
0~ 100.0%(100.0%)
P61.10 
Power limit selection
0~2 (1)
P61.09