EasyManuals Logo

Megmeet MV600L Series User Manual

Megmeet MV600L Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
70
MV600L-4T45 >= 35.0 >= 10 /
MV600L-4T55 >= 43.0 >= 7.5 /
MV600L-4T75 >= 60.0 >= 6 /
MV600L-4T90 >= 72 >= 5.5 MDBU-4-200, 1
MV600L-4T110 >= 88 >= 5.5 MDBU-4-200, 1
MV600L-4T132 >= 104 >= 3.6 MDBU-4-280, 1
MV600L-4T160 >= 128 >= 2.8 MDBU-4-200, 2
MV600L-4T200 >= 144 >= 2.8 MDBU-4-200, 2
MV600L-4T220 >= 176 >= 2.0 MDBU-4-280, 2
MV600L-4T280 >= 216 >= 2.0 MDBU-4-280, 2
MV600L-4T315 >= 264 >= 1.8 MDBU-4-200, 3
MV600L-4T355 >=284 >= 1.5 MDBU-4-280, 3
MV600L-4T400 >= 312 >= 1.5 MDBU-4-280, 3
The connecting wire between the braking units and drive, and between the braking units and braking resistors
shall be within 5m. If it is longer than 5m, twisted pair wire shall be adopted. The maximum wire length is 10m.