EasyManuals Logo

Metso ND9000P User Manual

Metso ND9000P
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
5(19)
Table 1. ND9000P GSD modules.
GSD mod-
ule name
control system output control system input
SP (short) bytes 1-4: SP.VALUE: Valve position
setpoint in AO block AUTO mode
(default mode), IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
none
SP (long) bytes 1-4: SP.VALUE: Valve position
setpoint, IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
none
RCAS_IN+
RCAS_OUT
bytes 1-4: RCAS_IN.VALUE: Valve
position setpoint in RCAS mode,
IEEE-754 float
byte 5: RCAS_IN.STATUS: The
status of the valve position setpoint.
Unsigned integer 8.
See table 2.
bytes 1-4:
RCAS_OUT.VALUE:
Feeds back the SP or
RCAS_IN, depending
on the mode, IEEE-754
float
byte 5:
RCAS_OUT.STATUS.
Unsigned integer 8.
See table 2.
SP+READB
ACK+POS_
D
bytes 1-4: SP.VALUE: Valve position
setpoint in AO block AUTO mode
(default mode), IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
bytes 1-4: READ-
BACK.VALUE: Valve
position measurement,
IEEE-754 float.
byte 5: READ-
BACK.STATUS: The
status of the valve
position measurement.
Unsigned integer 8.
See table 2.
byte 6: POS_D.VALUE:
Limit information from
the limit switches or
calculated from the
position sensor. Un-
signed integer 8. The
values are:
1 = closed
2 = opened
3 = intermediate
byte 7:
POS_D.STATUS:
Unsigned integer 8.
SP+CHECK
BACK
bytes 1-4: SP.VALUE: Valve position
setpoint in AO block AUTO mode
(default mode), IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
Bytes 1-3: CHECK-
BACK: diagnostic sig-
nal, bit-enumerated, 3
bytes. See table 3.
SP+READB
ACK+POS_
D+CHECKB
ACK
bytes 1-4: SP.VALUE: Valve position
setpoint in AO block AUTO mode
(default mode), IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
bytes 1-4: READ-
BACK.VALUE
byte 5: READ-
BACK:STATUS
byte 6: POS_D.VALUE
byte 7:
POS_D.STATUS
bytes 8-10: CHECK-
BACK
RCAS_IN+
RCAS_OUT
+CHECKBA
CK
bytes 1-4: RCAS_IN.VALUE: Valve
position setpoint in RCAS mode,
IEEE-754 float
byte 5: RCAS_IN.STATUS: The
status of the valve position setpoint.
Unsigned integer 8.
See table 2.
bytes 1-4:
RCAS_OUT.VALUE:
Feeds back the SP or
RCAS_IN, depending
on the mode, IEEE-754
float
byte 5:
RCAS_OUT.STATUS.
Unsigned integer 8.
GSD mod-
ule name
control system output control system input
bytes 6-8: CHECK-
BACK
SP+RIN+R
B+ROUT+P
OS_D+CB
bytes 1-4: SP.VALUE: Valve position
setpoint in AO block AUTO mode
(default mode), IEEE-754 float
byte 5: SP.STATUS: The status of
the valve position setpoint. Unsigned
integer 8. In normal case, use value
0x80. See table 2.
bytes 6-9: RCAS_IN.VALUE: Valve
position setpoint in RCAS mode,
IEEE-754 float
byte 10: RCAS_IN.STATUS: The
status of the valve position setpoint.
Unsigned integer 8.
See table 2.
bytes 1-4: READ-
BACK.VALUE
byte 5: READ-
BACK.STATUS
bytes 6-9:
RCAS_OUT.VALUE
byte 10:
RCAS_OUT.STATUS
byte 11:
POS_D.VALUE
byte 12:
POS_D.STATUS
bytes 13-15: CHECK-
BACK
The STATUS byte and the CHECKBACK mappings are
listed in the tables 2 and 3.
Table 2. Status byte mapping.
Status
byte in
case
that the
limit
bits are
zeros
Quali
ty
Bits
Additional
information
Bits
Limit
Bits
Meaning
7 6 5 4 3 2 1 0
0x00 0 0 0 0 0 0 x x bad
0x04 0 0 0 0 0 1 x x bad, configuration error
0x08 0 0 0 0 1 0 x x bad, not connected
0x0C 0 0 0 0 1 1 x x bad, device failure
0x10 0 0 0 1 0 0 x x bad, sensor failure
0x14 0 0 0 1 0 1 x x bad, no communication (last
usable value)
0x18 0 0 0 1 1 0 x x bad, no communication (no
usable value)
0x1C 0 0 0 1 1 1 x x bad, out of service
0x40 0 1 0 0 0 0 x x uncertain
0x44 0 1 0 0 0 1 x x uncertain, last usable value
0x48 0 1 0 0 1 0 x x uncertain, substituted value
0x4C 0 1 0 0 1 1 x x uncertain, initial value
0x80 1 0 0 0 0 0 x x good
0x84 1 0 0 0 0 1 x x good, Update event (change of
parameters)
0xA0 1 0 1 0 0 0 x x good, go into failsafe position
(command)
0xA4 1 0 1 0 0 1 x x good, maintenance required
0xC0 1 1 0 0 0 0 x x good (cascade)
0xC4 1 1 0 0 0 1 x x good (cascade), initialization
confirmed
0xC8 1 1 0 0 1 0 x x good (cascade), initialization
requested
0xCC 1 1 0 0 1 1 x x good (cascade), rcas mode not
requested
0xD8 1 1 0 1 1 0 x x good (cascade), local operation
has priority
0xE0 1 1 1 0 0 0 x x good (cascade), go into failsafe
position (command)
x x x x x x 0 0 value is not limited
x x x x x x 0 1 value is low limited
x x x x x x 1 0 value is high limited
x x x x x x 1 1 value is constant
x = could be any (0 or 1)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Metso ND9000P and is the answer not in the manual?

Metso ND9000P Specifications

General IconGeneral
BrandMetso
ModelND9000P
CategoryController
LanguageEnglish

Related product manuals