Table 1: Indoor unit branch pipes selection (a~f)
A: Capacity of indoor units (kW)
A (kW)
Gas Side(Φ)
Liquid Side(Φ)
Wall mounted 1.5~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Wall mounted 5.6
15.9(Flaring nut)
9.5(Flaring nut)
Four way cassette type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Four way cassette type 5.6~8.0
15.9(Flaring nut)
9.5(Flaring nut)
One way cassette type 1.8~4.5
12.7(Flaring nut)
6.4(Flaring nut)
One way cassette type 5.6
15.9(Flaring nut)
9.5(Flaring nut)
Low static pressure 1.8~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Low static pressure 5.6
15.9(Flaring nut)
9.5(Flaring nut)
Thin duct type 7.1
12.7(Flaring nut)
6.4(Flaring nut)
A5 duct type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
A5 duct type 5.6~8.0
15.9(Flaring nut)
9.5(Flaring nut)
A5 duct type 9.0~14.0
15.9(Flaring nut)
9.5(Flaring nut)
Console Type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Two-way Cassette Type 2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Two-way Cassette Type 5.6~7.1
15.9(Flaring nut)
9.5(Flaring nut)
Ceiling And Floor Type 3.6~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Ceiling And Floor Type 5.6~16.0
15.9(Flaring nut)
9.5(Flaring nut)
Expose And Concealed Floor-standing type
2.2~4.5
12.7(Flaring nut)
6.4(Flaring nut)
Expose And Concealed Floor-standing type
5.6~8.0
15.9(Flaring nut)
9.5(Flaring nut)
Note: The maximum length of the branch pipe should not be longer than 15m.
Table 2: Indoor unit main pipes selection (L1~L5)
Total capacity of
downstream indoor units
(kW)
Main pipe size(mm)
Branch Pipe
Gas pipe
Liquid pipe
A16.6
Φ15.9
Φ9.5
FQZHN-01C
16.6≤A23
Φ19.1
Φ9.5
FQZHN-01C
Table 3: Main pipes selection (L1)
Total capacity of
outdoor units
(kW)
When the equivalent length of all liquid and air
pipes < 90m
When the equivalent length of all liquid and air
pipes ≥ 90m
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
gas side
(mm)
liquid side
(mm)
The first line
branch pipe
A16
Φ15.9
Φ9.5
FQZHN-01C
Φ19.1
Φ9.5
FQZHN-01C
16≤A23
Φ19.1
Φ9.5
FQZHN-01C
Φ22.2
Φ9.5
FQZHN-02C
Note: Main pipe L1 can be selected form table 2 and table 3, the larger size should be finally selected.
The straight distance between copper pipe turning and the contiguous branch pipe is at least 0.5m.
The straight distance between the contiguous branch pipes is at least 0.5m.
The straight distance which the branch pipes connected to the indoor unit is at least 0.5m.
Table 4: Outdoor unit pipe connection
Piping side
MODEL
Outdoor unit pipe connection (mm)
Gas Side
Liquid Side
80 model
Φ15.9
Φ9.5
105 model
Φ15.9
Φ9.5
120 model
Φ15.9
Φ9.5
140 model
Φ15.9
Φ9.5
160 model
Φ19.1
Φ9.5
Outdoor Unit
Maximum Quantity of
Indoor unit
Total Capacity of Indoor unit
80 model
4
45%~130%
105 model
5
45%~130%
120 model
6
45%~130%
140 model
6
45%~130%
160 model
7
45%~130%
If ODU connect only one IDU, the capacity of IDU should be not more than ODU.

Table of Contents

Other manuals for Midea MDV-V80W/DN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MDV-V80W/DN1 and is the answer not in the manual?

Midea MDV-V80W/DN1 Specifications

General IconGeneral
BrandMidea
ModelMDV-V80W/DN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals