MCAC-VTSM-2014-10 R410A All DC Inverter Mini VRF
Troubleshooting 91
7.11 P3: Compressor current protection (for all models)
It will protect when input current is more than 30A. It will recover when input current is less than 30A.
It will recover automatically.
`
LED displays P3
Input current protection
Check whether the input current of the power wire is more
than 30A.
Check cooling system is normal or not.
YES
Check whether the outdoor ambient temperature is too high.
YES
Stop the unit.
NO
NO
Check whether the outdoor unit ventilates well.
YES
Make the outdoor unit
ventilates well.
NO
Whether the heat exchanger needs cleaning or not.
YES
Clean heat exchanger.
NO
If the refrigerant pipe is blocked or not?
YES
Remove the refrigerant pipe and then use
high pressure nitrogen or refrigerant to blow
the pipe. Vacuum the pipe then add the
refrigerant again.
Replace the outdoor PCB.