R410A All DC Inverter Mini VRF MCAC-VTSM-2014-10
86 Troubleshooting
7.6 E7: Discharge Temperature Sensor Malfunction (only for 80/105 models.)
1. How to check whether the sensor is normal:
Using a multi-meter to measure resistance, if the resistance is too small, the sensor is short circuit, if the resistance in
certain temperature is not consistent with attached table 2, the sensor is damaged.
2. The phenomenon of the system contains air or nitrogen :
The high pressure is higher than normal value, current is larger than normal value, discharge temperature is higher than
normal value, compressor makes noise, pressure meter do not display steady.
LED displays E7
Discharge sensor malfunction.
Check whether discharge temperature sensors head is
inside the sleeve or its wiring is connected to the main PCB
properly.
NO
Connect again.
YES
Check whether the discharged sensor is normal.
NO
Replace discharge sensor.
YES
Check the operation conditions of the unit meets the
operation requirementenvironment temperature,
airflow of the heat exchanger, etc.
NO
Belongs to the normal protection.
Check whether the refrigerant is charged too much.
NO
Confirm the refrigerants weight again.
YES
Replace the main PCB.
YES
Check whether the 4-way valve is normal.(No air mixed
up or bad action phenomenon. )
NO
Replace 4-way valve.
YES

Table of Contents

Other manuals for Midea MDV-V80W/DN1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MDV-V80W/DN1 and is the answer not in the manual?

Midea MDV-V80W/DN1 Specifications

General IconGeneral
BrandMidea
ModelMDV-V80W/DN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals