EasyManuals Logo

Midea MSC-07CRN1 User Manual

Midea MSC-07CRN1
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Service manual
21
8.7 Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge
indicates 0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher
than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will
not be necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be
discharged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MSC-07CRN1 and is the answer not in the manual?

Midea MSC-07CRN1 Specifications

General IconGeneral
BrandMidea
ModelMSC-07CRN1
CategoryAir Conditioner
LanguageEnglish

Related product manuals