EasyManua.ls Logo

Midea V6R VRF Series

Midea V6R VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V6R VRF 50Hz
149
2.34 U4: Indoor unit refrigerant pipe and signal cable connection are inconsistent
Digital display output
Description
Indoor unit refrigerant pipe and signal cable connection are inconsistent.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition:
Indoor unit refrigerant pipe and signal cable connection are inconsistent.
Recover condition:
Indoor unit refrigerant pipe and signal cable connection are consistent.
Reset method: Manually restart.
Possible causes
Indoor unit refrigerant pipe and signal cable connection are inconsistent.
Procedure
U4
Check the indoor unit refrigerant pipe
and signal cable connection are correct.

Table of Contents

Related product manuals