V6R VRF 50Hz
88
Midea
V6R
Series Service Manual
Procedure
E0
ODU addresses on switch ENC1 are set
incorrectly
1
Yes
Set the ODU addresses correctly
No
Communication wires between ODUs are
not connected properly
2
Yes
Ensure the communication wires are
two-core shielded cable and are
connected properly
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes
Ensure the wires are connected properly
No
Replace the outdoor main PCB resolves
the error
No
Replace the electric control box
communication terminals block
Notes:
1. The master unit address should be set as 0, slave units’ addresses should be set from 1 to 2, and the addresses should not be repeated within one system.
2. All the wires for H1, H2, E connections should be three-core shielded cable, the wiring should be connected according to polarity (H1 to H1, H2 to H2), and
the wiring should not be open or short circuited.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6R VRF Series and is the answer not in the manual?

Midea V6R VRF Series Specifications

General IconGeneral
BrandMidea
ModelV6R VRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals