Should settings be changed from default, please enter and record new setting in ‘Commissioning/Field settings record sheet’ below. This will ease resetting in the future
should the system use change or the circuit board need to be replaced.
Commissioning/Field settings record sheet
Main remote controller screen Parameters Default setting
Field
setting
Notes
DHW DHW *4 Eco On/O *5 O
Boost On/O —
DHW max. temp.
40°C to 55/60/65/70°C *6
50°C
Max. temp. drop
5°C to 40°C
10°C
Max. operation time
30 to 120 min.
60 min.
Interval 30 to 120 min. 30 min.
Volume
Large / Standard
Standard *7
Schedule On/O O
Always o
On/O
O
Legionella prevention *4 Legionella
On/O
On
Hot water temp.
60°C to 70°C *6
65°C
Start time 00:00 to 23:00 03:00
Duration 1 to 120 min. 30 min.
Frequency
1 to 30 days
15 days
Max. operation time
1 to 5 h
3 h
Heating
/ Cooling
*3
Heating / Cooling Zone 1 heating room temp.
10°C to 30°C
20°C
Zone 2 heating room temp. *1
10°C to 30°C
20°C
Zone 1 heating ow temp.
20°C to 60/70/75°C
45°C
Zone 2 heating ow temp. *2
20°C to 60/70/75°C
35°C
Zone 1 cooling ow temp. *3
5°C to 25°C
15°C
Zone 2 cooling ow temp. *3
5°C to 25°C
20°C
Zone 1 heating weather compensation
curve
−9°C to +9°C 0°C
Zone 2 heating weather compensation
curve *2
−9°C to +9°C 0°C
Zone 1 cooling weather compensation
curve
−9°C to +9°C 0°C
Zone 2 cooling weather compensation
curve *2
−9°C to +9°C 0°C
Schedule On/O O
Always o
On/O
O
Heating / Cooling
Heating / Cooling
Heating
Zone 1 control logic Heating room temp./ Heating ow temp./
Heating weather compensation curve / Cooling
ow temp./ Cooling weather compensation
curve
Heating weather
compensation
curve
Zone 2 control logic *2 Heating room temp./ Heating ow temp./
Heating weather compensation curve / Cooling
ow temp./ Cooling weather compensation
curve
Heating weather
compensation
curve
Auto change over
On/O
O
Weather
compensation
curve
(Heating)
Hi ow
temp. set
point
Zone 1 outdoor ambient temp. −30°C to +33°C *8 −15°C
Zone 1 ow temp. 20°C to 60/70/75°C 50°C
Zone 2 outdoor ambient temp. *2
−30°C to +33°C *8
−15°C
Zone 2 ow temp. *2
20°C to 60/70/75°C
40°C
Lo ow
temp. set
point
Zone 1 outdoor ambient temp.
−28°C to +35°C *9
20°C
Zone 1 ow temp.
20°C to 60/70/75°C
25°C
Zone 2 outdoor ambient temp. *2
−28°C to +35°C *9
20°C
Zone 2 ow temp. *2
20°C to 60/70/75°C
25°C
Adjust Zone 1 outdoor ambient temp.
−29°C to +34°C *10
—
Zone 1 ow temp.
20°C to 60/70/75°C
—
Zone 2 outdoor ambient temp. *2
−29°C to +34°C *10 —
Zone 2 ow temp. *2
20°C to 60/70/75°C —
Weather
compensation
curve (Cooling)
Hi ow
temp. set
point
Zone 1 outdoor ambient temp.
10°C to 46°C
35°C
Zone 1 ow temp.
5°C to 25°C
15°C
Zone 2 outdoor ambient temp. *2
10°C to 46°C
35°C
Zone 2 ow temp. *2
5°C to 25°C
20°C
Lo ow
temp. set
point
Zone 1 outdoor ambient temp.
10°C to 46°C
25°C
Zone 1 ow temp.
5°C to 25°C
25°C
Zone 2 outdoor ambient temp. *2
10°C to 46°C
25°C
Zone 2 ow temp. *2
5°C to 25°C
25°C
Menu Energy Energy monitor
Consumed electrical energy/Delivered energy
—
Holiday Schedule On/O/Set time —
DHW *4 On/O O
Heating / Cooling *3
On/O
On
Setting Language EN/CZ/DA/DE/ET/ES/FR/HR/IT/LV/LT/HU/NL/NO/PL/PT/RO/SK/SI/FI/SV/TR/EL/BG EN
Room
sensors
Zone sensor selection *2 Zone 1/Zone 2 Zone 1
Zone 1 programme TH1/Main RC/Room RC1-8/“Time/Zone” TH1
Zone 2 programme *2 TH1/Main RC/Room RC1-8/“Time/Zone” TH1
Display Temp. (°C) → (°F) On/O O
Touch
screen
Clean screen On/O O
Calibrate screen On/O O
Brightness Low / Mid / Hi Mid
Backlight time 5sec./10sec./20sec./30sec./60sec./Always on 30sec.