24 HIGH-SPEED INPUT/OUTPUT FUNCTION
24.6 General-purpose Input Functions
285
24
General-purpose input function parameters
This section explains the general-purpose input parameters.
Set the input response time parameters in GX Works3.
Parameter setting
This section explains how to set the input response time parameters.
Set the input response time.
Navigation window [Parameter] [FX5UCPU] [Module Parameter] [Input Response Time]
Window
Displayed items
Parameters are enabled when the CPU module is powered ON or after a reset.
Item Description Setting range Default
Response Type Select the input response time between 1 point unit and 8
point unit.
High-Speed: Unit of 1 point
Normal: Unit of 8 points
High-Speed
Normal
X0 to X377 Set the input response time. No Setting
10micro-s (μs)
50micro-s (μs)
•0.1ms
•0.4ms
•0.6ms
•1ms
•5ms
10ms
20ms
70ms
10ms

Table of Contents