118
5 INSTALLATION AND WIRING
5.5 Connection Method for the Extension Base Unit
When the Q6B is connected between the RQ extension base unit and the Q5B
The 5VDC output voltage of the power supply module on the Q6B is set to 4.90VDC (minimum value).
Therefore, the Q5B can be used when the voltage drop at the extension cable is 0.15VDC or lower (4.90VDC - 4.75VDC =
0.15VDC).
Diagonal lines show the power supply modules.
Symbol Description
V Voltage drop at the extension cable between the RQ extension base unit and the Q5B
In Current consumption (5VDC) when the Q5B is used as the extension level n+2 (n = 1 to 5), n: Extension level for the Q6B
(Sum total of the current consumption by the Q5B and current consumption by I/O modules and intelligent function modules
mounted on the Q5B)
Rn Resistance value for the extension cable between the RQ extension base unit and the Q6B or the Q6B and the Q6B
Rn+1 Resistance value for the extension cable between the Q6B and the Q5B
Mounting position Sum total (V) of the voltage drop at the extension cable from the main
base unit to the IN connector of the Q5B
Q6B Q5B
Extension level 2 Extension level 3 V=(R1+R2)I1
Extension level 2 to 3 Extension level 4 V=(R1+R2+R3)I2
Extension level 3 to 4 Extension level 5 V=(R1+R2+R3+R4)I3
Extension level 4 to 5 Extension level 6 V=(R1+R2+R3+R4+R5)I4
Extension level 5 to 6 Extension level 7 V=(R1+R2+R3+R4+R5+R6)I5
Q6B
Q6B
Q5B
In
V
Rn+1
Rn
Main base unit
RQ extension base
unit
Extension level n
Extension level n+1
Extension level n+2