128
5 INSTALLATION AND WIRING
5.7 Wiring
Wiring a connector
This section describes how to wire connectors for external devices.
Applicable connectors
The following reference products are the connector types and crimping tool for a module.
40-pin connectors
40-pin connector crimping tool
For how to wire the connector and how to use the crimping tool, contact the manufacturer.
Wiring method
A6CON1, A6CON4
Type Model Applicable wire size
Soldering type connector (straight type) A6CON1 0.088 to 0.3 (28 to 22 AWG) (stranded wire)
Crimping type connector (straight type) A6CON2 0.088 to 0.24 (28 to 24 AWG) (stranded wire)
Soldering type connector (dual purpose (straight/oblique) type) A6CON4 0.088 to 0.3 (28 to 22 AWG) (stranded wire)
Manufacturer Type Model Contact
FUJITSU COMPONENT LIMITED Crimping tool FCN-363T-T005/H www.fujitsu.com/jp/group/fcl/en/
1. Loosen the four fixing screws on the connector and
remove the screws. Open the connector cover from the
connector side.
2. Solder the wires and coat them with heat shrinkable
tubes (1).
3. Check the terminal layout and wire them to the
connector. When the connector is plugged into an I/O
module, an FG wire needs not to be installed.
(1)