5 INSTALLATION AND WIRING
5.7 Wiring
129
5
A6CON2
The following table shows the specifications of the FCN-363T-T005/H used for the A6CON2.
Wiring of the A6CON2 requires the special tool.
For how to use and adjust the tool, contact the manufacturer.
Arrangement for a flat cable is in the order of A1 B1 A2 
(The following figure shows a connector viewed from the plug-in side.)
4. Place the connector on one side of the connector cover
and put the fixing screws through the screw holes.
Cover another connector cover onto the connector.
5. Tighten the four screws.
Applicable wire size Cross-section area of
wire
Crimp height Sheath outside
diameter of wire
Length of stripped wire
part
AWG24 0.20 to 0.24 1.25 to 1.30 1.2 or less 3.0 to 4.0
AWG26 0.13 to 0.16 1.20 to 1.25 1.2 or less 3.0 to 4.0
AWG28 0.088 to 0.096 1.15 to 1.20 1.2 or less 3.0 to 4.0
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A09 A08 A07 A06 A05 A04 A03 A02 A01
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01