5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.1 System Configured by a Safety CPU
■Wiring diagram and parameter settings
<CCIEF remote (1): SR_IO1>
Wire the light curtain and electromagnetic contactors to safety remote I/O module as follows. For details on the terminal block,
refer to the following.
CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
Above [1] to [4] are connected to the one with same numbers.
*1 Connect two points (PNP output) of the Type 4 light curtain control output to between input and COM.
*2 Use two electromagnetic contactors operatable by 24VDC and 0.5A.
*3 Connect normally closed contact of the electromagnetic contactor between the input terminal and test pulse terminal.
*4 Create a dual wiring.
A1 +24V
[1]
[1]
[2]
[3]
[4]
[2]
[3]
[4]
A2 +24V
A3 24G
A5 FG
A4 24G
A1 +24V
A2 +24V
A3 24G
A5 FG
A4 24G
3X2
4X3
5X4
6X5
60 COM-
19 IO24V
20 IO24G
23 T0
24 T1
19 IO24V
20 IO24G
1Y0
2 COM-
3Y1
4 COM-
5Y2
6 COM-
L3
L2
L1
FG
FG
0V
0V
*4
24VDC
Terminal block for power supply and FG (input)
Spring clamp terminal block (input)
Spring clamp terminal block (output)
24VDC
24VDC
CCIEF remote (1)
NZ2GFSS2-32D
Network No.1
Station No.1
CCIEF remote (1)
NZ2EXSS2-8TE
Network No.1
Station No.1
24VDC
Light curtain
*1
Optical transmitter
Optical receiver
Muting lamp
Synchronization positive
Synchronization positive
Synchronization negative
Synchronization negative
24VDC
24VDC
Control output 1
Control output 2
Electromagnetic
contactor
*2*3
Electromagnetic
contactor
*2*3