5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.1 System Configured by a Safety CPU
139
5
For electromagnetic contactors, set the parameters as follows.
*1 Adjust the values of input response time, input dark test pulse off time, and output dark test pulse off time according to the installation
environment and wiring length.
*2 Set double input discrepancy detection time to 100ms for mechanical switches and 20ms for sensor inputs as standard.
*3 For details on each setting range, refer the following manual.
CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
*4 Always set the parameters like this for this case example.
Safety devices and safety labels to be used
To create a safety program, use the safety devices and standard/safety shared labels listed in the table below.
Item Setting details
*3
Transmission interval monitoring time 24ms
Wiring selection of input X0 and X1 Not used
Wiring selection of input X2 Double wiring (NC/NC)
*4
Wiring selection of input X3 Double wiring (NC/NC)
*4
Wiring selection of input X4 to XB Double wiring (NC/NC)
*4
Wiring selection of input XC to X1F Not used
Input response time X0 and X1 1ms
Input response time X2
*1
1ms
Input response time X3
*1
1ms
Input response time X4 to XB
*1
1ms
Input response time XC to X1F
*1
1ms
Double input discrepancy detection time X0_X1
*2
1ms
Double input discrepancy detection time X2_X3
*2
100ms
Double input discrepancy detection time X4_X5 to XA_XB
*2
100ms
Double input discrepancy detection time XC_XD to X1E_X1F
*2
1ms
Input dark test execution setting X0 and X1 Do not perform
*4
Input dark test execution setting X2 and X3 Perform
*4
Input dark test execution setting X4 to XB Do not perform
*4
Input dark test execution setting XC to X1F Do not perform
*4
Input dark test pulse OFF time
*1
400s
Number of pulse output for input dark test 1 time
Ext. module 1_Wiring selection of output Y0 Double wiring (Source/Source)
*4
Ext. module 1_Wiring selection of output Y1 Double wiring (Source/Source)
*4
Ext. module 1_Wiring selection of output Y2 to Y7 Not used
Ext. module 1_Output dark test execution setting Y0 Perform
*4
Ext. module 1_Output dark test execution setting Y1 Perform
*4
Ext. module 1_Output dark test execution setting Y2 to Y7 Do not perform
*4
Ext. module 1_Output dark test pulse OFF time Y0
*1
1ms
Ext. module 1_Output dark test pulse OFF time Y1
*1
1ms
Ext. module 1_Output dark test pulse OFF time Y2 to Y7
*1
1ms
Module External device Safety device/safety label
SR_IO1 Two-hand operation switch 1 (NC) SA\X6 or SA\X7
Two-hand operation switch 1 (NO) SA\X4 or SA\X5
Two-hand operation switch 2 (NC) SA\XA or SA\XB
Two-hand operation switch 2 (NO) SA\X8 or SA\X9
Contactor SA\Y0 and SA\Y1
Contactor (check for welding) SA\X2 or SA\X3
R_IO2 Reset switch reset_in