27 TROUBLESHOOTING
27.4 Error Code List
483
27
7F20H ASCIIBIN
conversion error
When the nonprocedural
or bidirectional protocol is
used, an ASCII code that
cannot be converted to
binary code was received.
When the nonprocedural
or bidirectional protocol is
used, an odd number of
bytes of data was
received during data
communications using
ASCII BIN conversion.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
When the nonprocedural or
bidirectional protocol is used
and data is communicated
using ASCII BIN
conversion, be sure to send
data in units of even bytes.

When data is received by
Conversion Variable of the
predefined protocol
function, the data
corresponding to the
Conversion Variable
cannot be converted to
binary numbers.
When data is received by
a Check code (ASCII
hexadecimal or ASCII
decimal) of the predefined
protocol function, the data
corresponding to the
check code cannot be
converted to binary
numbers.
PRO If the predefined protocol was
edited, check if the following
values match the packet format
of the target device:
Conversion, sign character,
number of decimals, delimiter,
number of digit for conversion
variable
Code type and data length of
check code
7F21H Receive header
area error
The command (frame)
part designation has an
error.
An ASCII code that
cannot be converted to
binary code was received.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7F22H Command error A nonexistent command,
subcommand, or device
was designated.
The remote password
length is incorrect.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7F23H MC protocol
message error
There is no data (ETX,
CR-LF, etc.) following the
character area, or the
designation was incorrect.
PRO Check and correct the
transmission message from
the target device and restart
data communications.
7F24H Sum check error The sum check code
calculated does not match
the sum check code
received.
The horizontal parity code
calculated does not match
the horizontal parity code
received.
The calculated check
code does not match the
received check code.
P/S Review the sum check code of
the target device.
Review the horizontal parity
code of the target device.
Review CRC-16 of the target
device.
If the predefined protocol was
edited, check if the following
values match the packet format
of the target device:
Processing method or code
type of the check code
Data length
Data flow
Complement calculation
Calculating range

Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined

Table of Contents