486
27 TROUBLESHOOTING
27.4 Error Code List
7FCFH System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7FD1H Modem function
error
The connection re-try
count designation is
incorrect.
CHn
ERR.
Set the connection re-try
count to 1 to 5.

7FD2H Modem function
error
The connection retry
interval designation is
incorrect.
CHn
ERR.
Set the connection retry
interval to 90 to 300
(seconds).

7FD3H Modem function
error
The initialization/
connection timeout
designation is incorrect.
CHn
ERR.
Set the time for the
initialization/connection
timeout to 1 to 60 (seconds).

7FD4H Modem function
error
The number of
initialization retries
designation is incorrect.
CHn
ERR.
Set the number of initialization
retires to 1 to 5.

7FD5H Modem function
error
The data No. for
initialization designation is
incorrect.
CHn
ERR.
Designate the registered
number of data for
initialization or '0'.

7FD6H Modern function
error
The data for connection of
the number specified in
the data No. for
connection designation is
incorrect.
CHn
ERR.
Review the line type. 
7FD7H Modem function
error
The data for connection of
the number specified in
the data No. for
connection designation is
incorrect.
CHn
ERR.
Review the external line
outgoing number.

7FD8H System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7FD9H Modern function
error
The line is connected to
the target, or the modem
has not been initialized.
CHn
ERR.
Upon the completion of the
modem initialization, connect
the line to the target device
(via public line) while the line
has not been connected yet.

7FDAH Modem function
error
The data No. for
connection designation is
incorrect.
CHn
ERR.
Designate the registered
number of data for connection.

7FDBH
System error The operating system of
C24 detected some error.
Page 490 Corrective actions
for system error
7FDCH Modern function
error
The data for connection of
the number specified in
the data No. for
connection designation is
incorrect.
CHn
ERR.
Review the data for
connection.

7FDDH Modem function
error
The connection timeout
error occurred.
CHn
ERR.
Review the telephone number
in the data for connection.
Check whether the connection
target is connectable.
Review the setting value for
the connection timeout.
Review the data for
initialization.

Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined

Table of Contents