3 REPLACEMENT OF I/O MODULE
3 - 57
(42)Specifications comparison between A1SX81-S2 (positive common) and QX41-S2
: Compatible, : Partially changed, : Incompatible
*1 Check the specifications of the sensor or switches to be connected to the QX41-S2.
*2 The following shows the derating chart.
Specifications A1SX81-S2 QX41-S2
Compat-
ibility
Precautions for replacement
Number of input points 32 points 32 points
Isolation method Photocoupler Photocoupler
Rated input voltage 24VDC 24VDC
Rated input current Approx. 7mA Approx. 6mA
The rated input current is
reduced.
*1
Operating voltage range
19.2 to 26.4VDC
(ripple ratio within 5%)
20.4 to 28.8VDC
(ripple ratio within 5%)
The operating voltage range
differs.
Maximum number of
simultaneous input points
Refer to the derating chart.
*2
Refer to the derating chart.
*2
Use it within the range shown in
the derating chart.
On voltage/on current 13VDC or more/3.5mA or more 15VDC or more/3mA or more
The on voltage/on current differ.
*1
Off voltage/off current 6VDC or less/1.7mA or less 5VDC or less/1.7mA or less
The off voltage differs.
*1
Input resistance Approx. 3.3k Approx. 3.6k
The input resistance is
increased.
*1
Response
time
Off on
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure the setting in the PLC
parameter dialog box.)
10ms is set by default.
Set the input response time of
parameter to the default value
(10ms).
On off
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure the setting in the PLC
parameter dialog box.)
10ms is set by default.
Common terminal
arrangement
32 points/common
(common terminal: 17, 18, 36)
32 points/common
(common terminal: B01, B02)
Operation indication On indication (LED) On indication (LED)
External connection
system
37-pin D-sub connector
(accessory)
40-pin connector
(sold separately)
Wiring change is required.
Applicable wire size
0.3mm
2
0.3mm
2
(A6CON1, A6CON4)
Current consumption 0.08A (typ. all points on) 0.075A (typ. all points on)
External dimensions 130(H)34.5(W)93.6(D)mm 98(H)27.4(W)90(D)mm
Weight 0.24kg 0.15kg
(A1SX81-S2) (QX41-S2)
On ratio (%)
On
ratio
Ambient temperature
100
90
80
70
60
50
40
010 20 30 40 5055
30
20
(%)
10
(31.25%) 24VDC
(18.75%) 28.8VDC