7 REPLACEMENT OF PROGRAM
7 - 33
7.6.3 Specifications comparison between MELSAP-II and MELSAP3
A part of the specifications of SFC program (MELSAP3) are different from those of SFC program
(MELSAP-II). Therefore, when utilizing the SFC program (MELSAP-II) of A/AnSCPU as the SFC
program (MELSAP3) of QCPU, select the QCPU that meets the specifications of the existing SFC
program (MELSAP-II).
7.6.4 MELSAP3 specifications comparison between QnASCPU and QCPU
A part of the specifications of SFC program (MELSAP3) are different from those of SFC program
(MELSAP3). Therefore, when utilizing the SFC program (MELSAP3) of QnASCPU as the SFC program
(MELSAP3) of QCPU, select the QCPU that meets the specifications of the existing SFC program
(MELSAP3).
*1 LDI/AND/OR/LDI/ANI/ORI instructions correspond besides LD instruction.
Contents
MELSAP-II MELSAP3
A/AnSCPU
QnUCPU
Q00U(J)CPU, Q01UCPU,
Q02UCPU
Q03UD(E)CPU, Q03UDVCPU,
Q04UD(E)HCPU, Q04UDVCPU,
Q06UD(E)HCPU, Q06UDVCPU
SFC block Max.256 Max.128 Max.320
Number of SFC steps Max.255 steps/block Max.128 steps/block Max.512 steps/block
Step transition monitoring timer Equipped (8 timers) None None
Contents
MELSAP3
QnA/QnASCPU
QnUCPU
Q00U(J)CPU, Q01UCPU,
Q02UCPU
Q03UD(E)CPU, Q03UDVCPU,
Q04UD(E)HCPU, Q04UDVCPU,
Q06UD(E)HCPU, Q06UDVCPU
SFC block Max.320 Max.128 Max.320
Number of SFC steps Max.512 steps/block Max.128 steps/block Max.512 steps/block
Step transition monitoring timer Equipped (10 timers) None None
SFC
program
start mode
setting
Act at block multi-activated Equipped None (Wait only) None (Wait only)
Act at step multi-activated Equipped None (Transfer only) None (Transfer only)
Periodic execution block
setting
Equipped None None
SFC
control
instructions
Forced transition check instruction
LD etc. TRn
*1
Equipped None None
LD etc. BLm\TRn
*1
Active step change instruction
SCHG (D) Equipped None None
Transition control instruction
SET TRn
Equipped None None
SET BLm\TRn
RST TRn
RST BLm\TRn
Block switching instruction
BRSET (S) Equipped None None
SFC program for program execution
management
Equipped None None
Program execution type setting Equipped None None