3 REPLACEMENT OF I/O MODULE
3 - 71
(7) Specifications comparison between A1SY40 and QY40P
ï‚¡: Compatible, : Partially changed, ï‚´: Incompatible
Specifications A1SY40 QY40P
Compat-
ibility
Precautions for replacement
Number of output points 16 points 16 points ï‚¡
Isolation method Photocoupler Photocoupler ï‚¡
Rated load voltage 12/24VDC 12/24VDC ï‚¡
Operating load voltage
range
10.2-30VDC
(peak voltage 30VDC)
10.2-28.8VDC
Voltage exceeding 28.8VDC is
not applicable.
Maximum load current 0.1A/point, 0.8A/common 0.1A/point,1.6A/common ï‚¡
Maximum inrush current 0.4A 10ms or less 0.7A 10ms or less ï‚¡
Leakage current at off 0.1mA or less 0.1mA or less ï‚¡
Maximum voltage drop
at on
1.0VDC (typ.) 0.1A
2.5VDC (MAX.) 0.1A
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
ï‚¡
Response
time
Off ï‚® on 2ms or less 1ms or less ï‚¡
On ï‚® off 2ms or less (resistance load)
1ms or less
(rated load, resistance load)
ï‚¡
Fuse None None -
Common terminal
arrangement
8 points/common
(common terminal: TB10, TB20)
16 points/common
(common terminal: TB18)
As the common is changed from
2 commons to 1 common, wiring
with a different voltage for each
common is not possible.
Operation indication On indication (LED) On indication (LED) ï‚¡
Fuse rating
(breaking capacity)
1.6A
(1 fuse/common)
Cannot be changed.
(breaking capacity: 50A)
--
These specifications are changed
to the protection function.
Fuse blown indication
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
Protection function -
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
ï‚¡
External
power
supply
Voltage
12/24VDC
(10.2 to 30VDC)
12-24VDC
(10.2 to 28.8VDC
ripple ratio within 5%)
Voltage exceeding 28.8VDC is
not applicable.
Current
8mA
(typ. 24VDC for one common)
MAX. 10mA (24VDC)
(all points on)
ï‚¡
External connection
system
20-point terminal block connector
(M3.5ï‚´7 screws)
18-point terminal block
(M3ï‚´6 screws)
ï‚´
Wiring change is required.
Applicable wire size
0.75 to 1.5mm
2
Core: 0.3 to 0.75mm
2
(outside diameter: 2.8mm or less)
ï‚´
Applicable solderless
terminal
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
R1.25-3
(Sleeved solderless terminal cannot
be used.)
ï‚´
Current consumption 0.27A (typ. all points on) 0.065A (typ. all points on) ï‚¡
External dimensions 130(H)ï‚´34.5(W)ï‚´93.6(D)mm 98(H)ï‚´27.4(W)ï‚´90(D)mm Wiring space is narrower.
Weight 0.19kg 0.16kg