3 REPLACEMENT OF I/O MODULE
3 - 74
(10)Specifications comparison between A1SY41P and QY41P
ï‚¡: Compatible, : Partially changed, ï‚´: Incompatible
Specifications A1SY41P QY41P
Compat-
ibility
Precautions for replacement
Number of output points 32 points 32 points ï‚¡
Isolation method Photocoupler Photocoupler ï‚¡
Rated load voltage 12/24VDC 12-24VDC ï‚¡
Operating load voltage
range
10.2 to 30VDC
(peak voltage 30VDC)
10.2 to 28.8VDC
Voltage exceeding 28.8VDC is
not applicable.
Maximum load current 0.1A/point 2A/common 0.1A/point 2A/common ï‚¡
Maximum inrush current 0.7A 10ms or less 0.7A 10ms or less ï‚¡
Leakage current at off 0.1mA or less 0.1mA or less ï‚¡
Maximum voltage drop
at on
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
0.1VDC (typ.) 0.1A
0.2VDC (MAX.) 0.1A
ï‚¡
Response
time
Off ï‚® on 1ms or less 1ms or less ï‚¡
On ï‚® off
1ms or less
(rated load, resistance load)
1ms or less
(rated load, resistance load)
ï‚¡
Surge suppressor Zener diode Zener diode ï‚¡
Fuse None None -
Common terminal
arrangement
32 points/common
(common terminal: A1, A2)
32 points/common
(common terminal: A01, A02)
ï‚¡
Operation indication On indication (LED) On indication (LED) ï‚¡
Protection function
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
Available
(overheat protection function,
overload protection function)
• The overheat protection function is
activated in increments of 1 point.
• The overload protection function is
activated in increments of 1 point.
ï‚¡
External
power
supply
Voltage
12/24VDC
(10.2 to 30VDC)
12-24VDC
(10.2 to 28.8VDC
ripple ratio within 5%)
Voltage exceeding 28.8VDC is
not applicable.
Current
12mA
(typ. 24VDC for each common)
20mA (24VDC) The current value is increased.
External connection
system
40-pin connector (accessory) 40-pin connector (sold separately) ï‚¡
Existing external wiring can be
used.
Applicable wire size
0.3mm
2
0.3mm
2
(A6CON1, A6CON4)
ï‚¡
Current consumption 0.141A (typ. all points on) 0.105A (typ. all points on) ï‚¡
External dimensions 130(H)ï‚´34.5(W)ï‚´93.6(D)mm 98(H)ï‚´27.4(W)ï‚´90(D)mm
Weight 0.15kg 0.15kg ï‚¡