EasyManua.ls Logo

Mitsubishi Electric MELSEC-Q Series - Page 150

Mitsubishi Electric MELSEC-Q Series
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 REPLACEMENT OF I/O MODULE
3 - 97
(b) Specifications comparison between A1SX48Y58 (output part) and QX48Y57(output part)
ï‚¡: Compatible, : Partially changed, ï‚´: Incompatible
Specifications
A1SX48Y58
(output specifications)
QX48Y57 (output specifications)
Compat-
ibility
Precautions for replacement
Number of output points 8 points 7 points
When 8 or more points are used,
use two QX48Y57 modules.
Isolation method Photocoupler Photocoupler ï‚¡
Output format Sink type Sink type ï‚¡
Rated load voltage 12/24VDC 12-24VDC ï‚¡
Operating load voltage
range
10.2 to 30VDC
(peak voltage 30VDC)
10.2 to 28.8VDC
Voltage exceeding 28.8VDC is
not applicable.
Maximum load current 0.5A/point, 2A/common 0.5A/point, 2A/common ï‚¡
Maximum inrush current 4A 10ms or less 4A 10ms or less ï‚¡
Leakage current at off 0.1mA or less 0.1mA or less ï‚¡
Maximum voltage drop at
on
0.9VDC (typ.) 0.5A,
1.5VDC (MAX.) 0.5A
0.2VDC (typ.) 0.5A,
0.3VDC (MAX.) 0.5A
ï‚¡
Response
time
Off ï‚® on 2ms or less 1ms or less ï‚¡
On ï‚® off
2ms or less
(resistance load)
1ms or less
(rated load, resistance load)
ï‚¡
Surge suppressor Zener diode Zener diode ï‚¡
Fuse rating
(breaking capacity)
3.2A
(1 fuse/common)
Cannot be changed.
(breaking capacity: 50A)
4A
(1 fuse/common)
Cannot be changed.
(breaking capacity: 50A)
ï‚¡
Fuse blown indication
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
Available
(LED turns on when a fuse is blown
and a signal is output to the CPU
module.)
Common terminal
arrangement
8 points/common
(common terminal: TB19)
7 points/common
(common terminal: TB18)
8 points/common is changed to 7
points/common.
External
power
supply
Voltage
12/24VDC
(10.2 to 30VDC)
12-24VDC (+20/-15%)
(ripple ratio within 5%)
Voltage exceeding 28.8VDC is
not applicable.
Current
60mA
(typ. 24VDC for each common)
10mA (24VDC) ï‚¡

Table of Contents