3 REPLACEMENT OF I/O MODULE
3 - 100
(8) Specifications comparison between A1SJ-56DR and QX40/QY10
(a) Specifications comparison between A1SJ-56DR (input part) and QX40
: Compatible, : Partially changed, : Incompatible
*1 Check the specifications of the sensor or switches to be connected to the QX40.
Specifications
A1SJ-56DR
(input specifications)
QX40
Compat-
ibility
Precautions for replacement
Number of input points 32 points 16 points
When 17 or more points are
used, use two QX40 modules.
Isolation method Photocoupler Photocoupler
Input format Sink input
Sink input
(positive common)
Rated input voltage 24VDC 24VDC
Rated input current Approx. 7mA Approx. 4mA
The rated input current is
reduced.
*1
Operating voltage range
19.2 to 26.4VDC
(ripple ratio within 5%)
20.4 to 28.8VDC
(ripple ratio within 5%)
The operating voltage range
differs.
Maximum number of
simultaneous input points
60% (10 points/common)
Simultaneously on
Simultaneously on (100%)
On voltage/on current 14VDC or more/3.5mA or more 19VDC or more/3mA or more
The on voltage and on current
differ.
*1
Off voltage/off current 6.5VDC or less/1.7mA or less 11VDC or less/1.7mA or less
The off voltage differs.
*1
Input resistance Approx. 3.3k Approx. 5.6k
The input resistance is
increased.
*1
Response
time
Off on
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure
the setting in the PLC
parameter dialog box.
)
10ms is set by default.
Set the input response time of
parameter to the default value
(10ms).
On off
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure
the setting in the PLC
parameter dialog box.
)
10ms is set by default.
Common terminal
arrangement
16 points/common
(common terminal: TB17, TB34)
16 points/common
(common terminal: TB17)
Operation indication On indication (LED) On indication (LED)
External connection
system
34-point terminal block connector
2 pieces (M3.56 screws)
18-point terminal block
(M36 screws)
Wiring change is required.
Applicable wire size
0.75 to 2mm
2
Core: 0.3 to 0.75mm
2
(outside diameter: 2.8mm or less)
Applicable solderless
terminal
R1.25-3.5, R2-3.5
RAV1.25-3.5, RAV2-3.5
R1.25-3
(Sleeved solderless terminal cannot
be used.)
Number of occupied I/O
points
128 points
(slot 0: Output 64 points,
slots 1 to 4: Empty 16 points)
16 points
(I/O assignment: Input 16 points)
-
Current consumption 0.22A (typ. all points on) 0.05A (typ. all points on) -
The module configuration differs.
Recalculate the current
consumption.
External dimensions 130(H)174.5(W)65.6(D)mm 98(H)27.4(W)90(D)mm Wiring space is narrower.
Weight 0.80kg 0.16kg