7 REPLACEMENT OF PROGRAM
7 - 3
(2) Comparison between QnASCPU and QCPU
ï‚¡: Compatible, :Partially changed, ï‚´: Incompatible
Item QnASCPU specifications
QCPU specifications and
precautions for replacement
Compat-
ibility
Reference
Sequence program
SFC program
• Each program is dealt as one file.
[Specification]
• Each program is dealt as one file.
 –
Instruction
• Dedicated instructions as display
(LED) instruction, status latch (SLT)
instruction, etc. are available.
[Specification]
• With "Change PLC type", instructions
are converted automatically except
some instructions.
[Measure]
• The instructions that cannot be
converted are changed to SM1255 and
SD1255 for QCPU. Therefore, program
modification is required.
Section 7.2
File register
• Data is stored in a memory card.
• One block is set in 32k points unit.
[Specification]
• Data is stored in a standard RAM or
memory card.
• One block is set in 32k points unit.
[Measure]
• Review the setting.
Section
7.7.11
Parameter
• Dedicated parameters for each
CPU are provided.
[Specification]
• Dedicated parameters for each CPU
are provided.
[Measure]
• Check and re-set the parameters since
specifications and functions differ
between the two CPUs.
Section 7.3
Special relay
• 1800 points of SM0 to SM1799 are
provided.
[Specification]
• 1800 points of SM0 to SM1799 are
provided.
[Measure]
• Review the points since some
specifications differ between the two
CPUs.
Section 7.4
Special register
• 1800 points of SD0 to SD1799 are
provided.
[Specification]
• 1800 points of SD0 to SD1799 are
provided.
[Measure]
• Review the points since some
specifications differ between the two
CPUs.
Section 7.5
Comment
• Comments are managed as a
common comment or program
original comment.
[Specification]
• For the QCPU, comments are managed
as common comments or comments by
program. (For the Basic model QCPU,
only comments by program (MAIN) are
managed.)
ï‚¡
Section
7.1.2
Writing programs to
ROM
• The boot run is executed with
program and parameter stored in a
memory card.
• One memory card can be installed.
[Specification]
• Replacement does not need to be
selected for the Universal Model QCPU
as the program memory is flash ROM.
• Boot run of the Universal Model QCPU
can be executed using an SD memory
card.
Section
7.7.12

Table of Contents