1 INTRODUCTION
1 - 5
Replacement procedures:
(1) Remove the existing AnS series modules together with the base unit, and use the
existing mounting holes to mount the upgrade tool (Base adapter) manufactured by
Mitsubishi Electric Engineering Co., Ltd. Then mount the Q series. (By mounting the
base adapter, it is not necessary to redo the mounting holes.)
If the existing base unit is mounted on a DIN rail, the replaced Q series base unit can be
directed installed, so a base adaptor is unnecessary.
(2) Mount the upgrade tool (Conversion adapter) manufactured by Mitsubishi Electric
Engineering Co., Ltd. on the mounted Q series I/O modules.
(3) Remove the terminal blocks wired from the existing AnS series I/O modules, and mount
the blocks on the conversion adapter. (The existing wiring is usable.)
(4) Programs are automatically converted* by changing the programmable controller type
from AnS/QnASCPU to QCPU using GX Developer.
Even if the module arrangement is changed, the I/O can be assigned to the same
number as before, which cuts out the need to modify the programs and slot number for
I/O module.
* Some instructions are not automatically converted. In case of intelligent function module or network module, programs and
parameters need be changed.
24V Y0 Y1 YE YF
CFCEC0 C10V
DC
AC
+
+
Use existing wiring
for I/O module
AC lamp DC lamp
FA-TH16YRA20 Yo to YF
24VDC
Existing AnS Series Q Series
Upgrade tool
(base adapter)
Upgrade tool
(conversion adapter)
FA goods
When replacing the AnS Series I/O module with the Q
Series I/O module, the FA goods conversion module