3 REPLACEMENT OF I/O MODULE
3 - 15
Point
When using the extension base unit of the A/QnA series, please refer to the following for details.
Transition from MELSEC-A/QnA (Large Type) Series to Q Series Handbook (Fundamentals)
L(NA)08043ENG
Interrupt module A1SI61 QI60
1) External wiring: changed
2) Number of slots: not changed
3) Program
Number of occupied I/O points: changed (32 points ï‚® 16 points)
4) Specifications
Rated input voltage: changed (12VDC is not applicable.)
Rated input current: changed (Approx.8mA Approx.6mA)
On voltage/on current: changed
Off voltage/off current: changed
Input resistance: changed
5) Function: changed
(condition setting: hardware switch ï‚® parameter)
Dummy module A1SG62 None
[Dummy module function]
Consider using the QG60 and I/O assignment setting.
Blank cover A1SG60 QG60 No restrictions
AnS/QnAS series model Q series alternative model
Product Model Model Remarks (restrictions)