3 REPLACEMENT OF I/O MODULE
3 - 33
(18)Specifications comparison between A1SX42 (24VDC) and QX42
: Compatible, : Partially changed, : Incompatible
*1 Check the specifications of the sensor or switches to be connected to the QX42.
*2 The following shows the derating chart.
Specifications A1SX42 QX42
Compat-
ibility
Precautions for replacement
Number of input points 64 points 64 points
Isolation method Photocoupler Photocoupler
Rated input voltage 12/24VDC 24VDC
Rated input current Approx. 2mA/Approx. 5mA Approx. 4mA
The rated input current is
reduced.
*1
Operating voltage range
10.2 to 26.4VDC
(ripple ratio within 5%)
20.4 to 28.8VDC
(ripple ratio within 5%)
Maximum number of
simultaneous input points
Refer to the derating chart.
*2
Refer to the derating chart.
*2
On voltage/on current 8VDC or more/2mA or more 19VDC or more/3mA or more
The on voltage/on current differ.
*1
Off voltage/off current 4VDC or less/0.6mA or less 11VDC or less/1.7mA or less
The off voltage/off current differ.
*1
Input resistance Approx. 5k Approx. 5.6k
The input resistance is
increased.
*1
Response
time
Off on
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure
the setting in the PLC
parameter dialog box.
)
10ms is set by default.
Set the input response time of
parameter to the default value
(10ms).
On off
10ms or less
(24VDC)
1ms/5ms/10ms/20ms/70ms or less
(Configure
the setting in the PLC
parameter dialog box.
)
10ms is set by default.
Common terminal
arrangement
32 points/common
(common terminal: 1B1, 1B2, 2B1,
2B2)
32 points/common
(common terminal: 1B01, 1B02,
2B01, 2B02)
Operation indication
On indication (LED)
32-point switching indication with the
switch
On indication (LED)
32-point switching indication with the
switch
External connection
system
40-pin connector 2 pieces
(accessory)
40-pin connector 2 pieces
(sold separately)
Existing external wiring can be
used.
Applicable wire size
0.3mm
2
0.3mm
2
(A6CON1, A6CON4)
Current consumption 0.09A (typ. all points on) 0.09A (typ. all points on)
External dimensions 130(H)34.5(W)93.6(D)mm 98(H)27.4(W)90(D)mm
Weight 0.28kg 0.18kg
(A1SX42) (QX42)
24VDC
26.4VDC
On ratio (%)
100
90
80
70
60
50
40
0102030405055
Ambient temperature
24VDC
30
20
26.4VDC
28.8VDC
ON
ratio/
common