8 - 24
8 AUXILIARY AND APPLIED FUNCTIONS
(3) When it does not pass (zero pass signal: M2406+20n ON) the zero point from
home position return start to deceleration stop by proximity dog ON to OFF, a
minor error "ZCT not set" (error code: 120) will occur, a deceleration stop is made
and home position return does not end normally. When a distance between home
position return start position and home position is near and a zero point is not
passed, select the proximity dog type 2.
(4) If home position return is executed in the proximity dog ON, a major error
"proximity dog signal is turning ON at the home position return start" (error code:
1003) will occur, the home position return is not executed. Use the proximity dog
type 2 in this case.
(5) When home position return retry function is not set, if home position return is
executed again after home position return end, a minor error "home position return
completion signal is turning ON at the proximity dog type home position return
start" (error code: 115) will occur, the home position return is not executed.
(6) If in-position signal (M2402+20n) does not turn ON, home position return is not
ended.