9 - 5 9 - 5
MELSEC-Q
9 UTILITY PACKAGE (GX Configurator-SC)
(6) Number of parameters that can be set in GX Configurator-SC
When multiple intelligent function modules are mounted, the number of
parameter settings must not exceed the following limit.
When intelligent function modules are
installed to:
Maximum number of parameter settings
Initial setting Auto refresh setting
Q00J/Q00/Q01CPU 512 256
Q02/Q02H/Q06H/Q12H/Q25HCPU 512 256
Q02PH/Q06PH/Q12PH/Q25PHCPU 512 256
Q12PRH/Q25PRHCPU 512 256
Q00UJ/Q00U/Q01UCPU 512 256
Q02UCPU 2048 1024
Q03UD/Q04UDH/Q06UDH/Q10UDH/
Q13UDH/Q20UDH/Q26UDH/Q03UDE/
Q04UDEH/Q06UDEH/Q10UDEH/
Q13UDEH/Q20UDEH/Q26UDEHCPU
4096 2048
CPU modules other than the above Not supported Not supported
MELSECNET/H remote I/O station 512 256
For example, if multiple intelligent function modules are installed to the
MELSECNET/H remote I/O station, configure the settings in GX Configurator so
that the number of parameter settings for all the intelligent function modules does
not exceed the limit of the MELSECNET/H remote I/O station. Calculate the total
number of parameter settings separately for the initial setting and for the auto
refresh setting.
The number of parameters that can be set for one module in GX Configurator-SC
is as listed below.
Target Module Initial setting Auto refresh setting
QJ71C24N 0 (Not used) 48 (Max.)
QJ71C24N-R2 0 (Not used) 49 (Max.)
QJ71C24N-R4 0 (Not used) 48 (Max.)
QJ71C24 0 (Not used) 48 (Max.)
QJ71C24-R2 0 (Not used) 49 (Max.)