11 - 44 11 - 44
MELSEC-Q
11 TROUBLESHOOTING
11.3.10 Communication error "PRO."
Symptom Cause Corrective action
MC
Bidirectional
Non
procedure
Pre-defined
• Communication error
signal "PRO" turned
on.
• Communications were
performed with a control
procedure different from the
Q series C24 communication
protocol setting.
Check the Q series C24 communication protocol
setting and the message from the external device
and match the settings, or correct the message and
restart data communications.
Use the communication monitoring function to check
the message from the external device.
Some of the data are
different from the control
procedure.
• Designated command does
not exist.
The device No. designation
is not the character count
corresponding to the
command.
The characters in the
message include a data
other than the "A to Z", "0 to
9", "
", and control data.
Check and correct the external device message and
restart data communications.
Use the communication monitoring function to check
the message from the external device.
Note
Only the data "0 to 9" and "A to F" can be handled
as character area data during communications
using an MC protocol (ASCII mode). Therefore,
when transmitting a character string as data,
convert the ASCII code of each character string to
2-byte binary code.
Examples)
• Transmitting the character "G"
The ASCII code for the character "G" is 47
H and
is transmitted as the two bytes 34
H, 37H.
• Transmitting the character "A"
The ASCII code for "A" is 41
H and is transmitted
as the two bytes 34
H, 31H.
If the ASCII code 41H for the character
"A" is transmitted unchanged, the Q series
C24 ASCII-BIN conversion will convert it to
A
H
(10) and pass it to the programmable
controller CPU.
A device No. outside the
designated range was
designated.
When designating a device, check "Device setting"
of the parameters written to the CPU and correct it to
a device No. within the designated range and restart
data communications.
• A remote RUN/STOP
request was issued while
remote STOP was applied
from another module.
Check if remote STOP is applied from another
module and restart data communications.