9 - 24 9 - 24
MELSEC-Q
9 UTILITY PACKAGE (GX Configurator-SC)
9.4.4 Modem function system setting/registration
[Purpose]
For data communication using the modem function, register system setting
values.
[Operating procedure]
• Online operation
[Monitor] screen
Modem function system setting
• Offline operation
[Flash ROM setting] screen
Modem function system setting
[Setting screen]
[Setting items]
Item
Buffer memory address
Reference section
CH1 CH2
Modem connection channel designation 2EH
User's Manual (Application)
Notification execution designation 2FH
Number of connection retries designation 30H
Connection retry interval designation (units: s) 31H
Initialization/connection timeout designation (units: s) 32H
Number of initialization retries designation 33H
Data No. for initialization designation 34H
Data No. for connection designation 35H
GX Developer connection designation 36H
No-communication interval time designation (units: min) 37H
RS / CS control yes/no designation 38H
Modem initialization time DR signal valid/invalid designation 2008H
Wait time of notification (units: s) 200AH
Circuit disconnect wait time (PLC CPU watch use) (units: s) 200EH
Remote password mismatch notification count designation 200CH
Remote password mismatch notification accumulated count designation 200DH
Auto modem initialization designation 2007H
Callback function designation 2001H
Callback denial notification accumulated count designation 2002H
Data No. for callback designation 1 to 10 2101H to 210AH