11 - 53 11 - 53
MELSEC-Q
11 TROUBLESHOOTING
11.3.16 Communication is not available via the modem.
Symptom Cause Corrective action MC
Non
procedure
protocol
Bidirectional
protocol
Pre-defined
Auto modem initialization
cannot be executed.
A modem initialization error occurs.
Check the error code and execute
processing accordingly.
Modem connection channel designation
is not performed.
Set Modem connection channel
designation.
There is an error in the switch settings in
the GX Developer.
Review the switch settings. Set it to
match the local station modem and the
TA.
Data cannot be
communicated with GX
Developer supporting the
Q series C24.
Communication protocol setting is
incorrect.
Set the communication protocol to MC
protocol, format 5.
Transmission setting does not match the
external device.
Review the transmission setting.
Communication rate does not match the
external device.
Review the communication rate setting.
The GX Developer does
not receive the callback
signals from the Q series
C24.
The product is not supported by the GX
Developer.
Confirm the GX Developer's S/W
version.
There was an error in the GX Developer
connection system.
Check the GX Developer's connection
system.
Set the connection system on “callback
reception waiting” and connect.
There is an error in the GX Developer
side's modem settings.
Set the modem's settings on "Auto
Reception."
• Callback connections
from the GX Developer
are refused by the Q
series C24.
There s an error in the GX Developer's
connection system.
Check the GX Developer's connection
system.
Correct the Q series C24's settings.
There is an error in the connection
system's telephone No.
Check the telephone No.
Change the telephone No. to the data
for callback.
When performing Auto
(callback: during fixed/
during designated
number) from the GX
Developer, connection to
the Q series C24 is
refused.
There is an error in the Q series C24
setting value.
Set the callback function designation on
the setting 1 to 3.
There is an error in the GX Developer's
connection system.
Check the GX Developer's connection
system.
Check the Q series C24's settings.
There is an error in the telephone No. of
the connection system.
Check the telephone No.
Change the telephone No. to the data
for callback.
It is possible to connect
from the GX Developer,
but callback from the Q
series C24 cannot be
performed.
The timer value for the status of the
modem used or the line is short.
Adjust each of the timer values for the
callback function on the GX Developer
side. (Line callback cancel wait time,
callback delay time)
There is a problem with the modem
specifications or settings.
Check the modem's specifications and
settings.