MELSEC-Q
11 TROUBLESHOOTING
11.3.2 The "RD" LED does not blink even after message transmission from the external
device.
Symptom Cause Corrective action
MC
Bidirectional
Non
procedure
Pre-defined
"RD" does not blink
even through an
external device is
transmitting a
message.
Signal lines are not
connected correctly.
Check if the Q series C24 and external
RD(RXD) and SD(TXD) signal lines are
cross connected.
Use the external device OPEN statement to
check if the opened port and the cable
connection port are matched.
• External device
transmission control
signals are not turned
ON.
Connect the wiring so that the "DR(DSR)",
"CS(CTS)", and other transmission control
signals are ready.
Note
Since the control signal specifications
depend on the device, connect the wiring
by seeing the instruction manual of the
device used.
If the message
passes through an
RS-232
RS-422
converter, modem,
etc., the signal is
interrupted at one of
the intervening
devices.
Check the specifications of the converter
and modem and recheck the settings and
wiring