MELSEC-Q
11 TROUBLESHOOTING
11.3.4 Transmission request does not make the "SD" LED blink.
Symptom Cause Corrective action
MC
Bidirectional
Non procedure
Pre-defined
• Although a
transmission request
was made, "SD" does
not blink.
Due to the OFF status of
the CS(CTS) signal, the Q
series C24 cannot transmit
data to the external
device.
While the CS(CTS) signal is OFF, the Q series C24
does not transmit data to the external device.
It must be ON when the external device is ready to
receive data.
• Due to transmission
control (DTR or DC
control), the external
device cannot receive
data.
Wait until the external device is ready to receive data.
When the waiting time is too long, check the external
device or cable condition.