5.
Handling
Component Equipment Modules MELSEC
GOT
This section shows how to enter the settings for
the
power supply module installed in the GOT.
0
When installing a power supply module in the GOT,
or
removing it from the GOT,
Not doing
so
could result in electric shock, damage to the module or malfunctioning.
@
DANGER
switch all phases of the external power supply
off
to the GOT and PC.
I
A
CAUTION
0
When wiring the power supply module, always check the rated voltage
of
the product
first, as well as the terminal layout, and make sure wiring is done correctly.
Connecting a power supply of the wrong voltage or wiring the module erroneously
could result in fire or breakdowns.
@=
@
Install the power supply module to the GOT, then fix it in place
by tightening the screws of the power supply module within
the range of specified torque,
39
to
59
Ncm
(4
to
6
kgcm).
To
remove the power supply module, loosen the screw, and
then reverse the installation procedure.
@
Connect the power supply module to the terminal base with
the power supply cable.
If
the power supply voltage is
100
VAC, set (short)
100
VAC on
the short side of the power supply terminal.
Connect the power cables grounded to the FG and LG termi-
nals.
If
external output is being used, connect the output terminal
and the equipment being used with power cables.
After completing the wiring, cover it with a protective cover to
make sure no one touches it.
5-16