15 Example of Communication in Compound System
15.1 When Remote Net Ver. 1 Mode is Used
210
FX3U-16CCL-M User's Manual
• Program to control remote I/O stations, remote device stations and intelligent device stations
Unit
error
M20
M35
Unit
ready
Reads the data link status
in intelligent device station
(SW0080).
M21
Data link
status in
master
station
M501
Y030
Y031
There is an error in data
link in the AJ65BTB1-16D
(Station No. 1)
Data link is being
executed in the
AJ65BTB1-16D
(Station No. 1)
Data link is being
executed in the FX
2N-
32CCL. (Station No. 2)
FNC 79
FROM
K0 H0680 K4M501 K1
M501
M502
M502
Normal link (station No. 1)
Link error (station No. 1)
Normal link (station No. 2)
Link error (station No. 2)
FNC 01
CALL
P10
FNC 01
CALL
P20
FNC 06
FEND
There is an error in
data link in the FX
2N-
32CCL. (Station No. 2)
M21
Data link status in
master station
Y040
Master station data link
error
Y032
Data link is being
executed in the FX3U-
64CCL. (Station No. 3)
M503
M503
Normal link (station No. 3)
Link error (station No. 3)
FNC 01
CALL
P30
There is an error in
data link in the FX
3U-
64CCL. (Station No. 3)
M8000
RUN monitor
Reads from the remote
input (RX) of the
AJ65BTB1-16D.
FNC 79
FROM
K0 H00E0 K4M100 K1
M100
M115
Y000
Y017
When inputs X00 to X0F
in the AJ65BTB1-16D
turn ON, outputs Y000 to
Y017 in the PLC turn ON.
Program for
communication
with the
A
J65BTB1-16D
(Station No. 1).
to
P10
FNC 02
SRET
Program for
communication
with the FX
2N-
32CCL (Station
No. 2).
M8000
RUN
monitor
FNC 79
FROM
K0 H00E2 K4M132 K2
FNC 78
TO
K0 H0162 K4M300 K2
FNC 78
TO
K0 H01E4 D100 K4
P20
Reads from remote input.
HE3 to HE2
(RX3F to RX20)
M163 to M132
FNC 79
FROM
K0 H02E4 D200 K4
To the next page
Reads from remote
register (RWr).
H2E7 to H2E4
(RWr7 to RWr4)
D203 to D200
Writes to remote output.
M331 to M300
H163 to H162
(RY3F to RY20)
Writes to remote register
(RWw).
D103 to D100
H1E7 to H1E4
(RWw7 to RWw0)

Table of Contents

Other manuals for Mitsubishi FX3U-16CCL-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U-16CCL-M and is the answer not in the manual?

Mitsubishi FX3U-16CCL-M Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U-16CCL-M
CategoryController
LanguageEnglish

Related product manuals