15 Example of Communication in Compound System
15.1 When Remote Net Ver. 1 Mode is Used
211
FX3U-16CCL-M User's Manual
11
Programming
12
Remote I/O
Communication
Example
13
Remote Device
Communication
Example
14
Int. Device
Communication
Example
15
Compound Sys.
Communication
Example
16
Troubleshooting
A
Version
Information
B
Setting Sheet
C
Differences with
FX
2N
-16CCL-M
Program for
communication
ith the FX3U-
64CCL (Station
No. 3).
P30
M8000
RUN
monitor
FNC 79
FROM
K0 H00E4 K4M164 K4
FNC 78
TO
K0 H0164 K4M332 K4
FNC 78
TO
K0 H01E8 D104 K8
FNC 79
FROM
K0 H02E8 D204 K8
M164
FX
3U
-64CCL (RX00)
Y060
X001
M332
Program for
confirming
operation of the
FX
3U-64CCL
(Station No. 3).
FNC 02
SRET
M132
FX
2N
-32CCL (RX00)
Y050
X000
M300
Program for
confirming
operation of the
FX
2N-32CCL
(Station No. 2).
FNC 02
SRET
From the previous page
Reads from remote input.
HE7 to HE4 (RX7F to
RX40)
M227 to M164
Reads from remote
register (RWr).
H2EF to H2E8 (RWrF to
RWr8)
D211 to D204
When RX00 in the FX
3U-
64CCL (station No. 3)
turns ON,
Y060 in the PLC turns ON.
When X001 in the PLC
turns ON,
RY00 in the FX
3U-64CCL
(station No. 3) turns ON.
Writes to remote output.
M395 to M332
H167 to
H164 (RY7F to RY40)
Writes to remote register
(RWw).
D111 to D104
H1EF to
H1E8 (RWwF to RWw8)
When RX00 in the FX
2N-
32CCL (station No. 2)
turns ON,
Y050 in the PLC turns ON.
When X000 in the PLC
turns ON,
RY00 in the FX
2N-32CCL
(station No. 2) turns ON.