[ IX Troubleshooting ]
- 160 -
HWE1018A GB
1. Error Code
Total capacity error
2. Error definition and error detection method
The model total of indoor units in the system with one outdoor unit exceeds limitations.
3. Error source, cause, check method and remedy,
7100
Error source Cause Check method and remedy
Outdoor unit (1) The model total of indoor units in the sys-
tem with one outdoor unit exceeds the fol-
lowing table.
1) Check the Qj (capacity code total) of indoor units
connected.
2) Check the Qj (capacity code) of the connected
indoor unit set by the switch (SW2 on indoor unit
board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the outdoor and the indoor units,
and change the setting of the Qj (capacity code).
(2) The model selection switches (SW5-1 - 5-
4) on the outdoor unit are set incorrectly.
Check the setting for the model selection switch
on the outdoor unit (Dipswitches SW5-1 - 5-4 on
the outdoor unit control board).
(3) The outdoor unit and the auxiliary unit
(OS) that is connected to the same system
are not properly connected.
Confirm that the TB3 on the OC and OS are properly
connected.
Qj
Model
250 model 50
500 model 100