[ VII Control ]
- 80 -
HWE1018A GB
2. Function of the switch (Indoor unit)
(1) Dipswitches
1) SW1,3
2) SW2,SW3-2,SW4
Switch Function
Function according to switch setting
OFF ON
Switch setting timing
OFF ON
Notes
SW1
SW3
SW7
1
2
3
4
5
6
7
8
9
10
1
2
3
4
1
2
3
4
5
6
7
9
10
8
Clogged filter detection
Filter check reminder
time setting
Remote display option
External input
Operation switching
Model setting
Capacity code
100h
Fan output
2500h
Thermo-ON signal
Available
Level
External input
Heat pump
MA remote controller
Cooling-only
Pulse
Not available Available
Not available Available
Not available Available
Refer to the combination with SW2
Not available
---
---
---
---
---
---
---
---
---
-
LEV setting conversion
function
Reset of the integrated
operation time
Valid/Invalid (fan belt)
Reset of the integrated
operation time
Valid/Invalid (fan motor)
--
---
---
-
--
-
--
While the unit is stopped
(Remote controller OFF)
Note 1. Setting timing for DIPSW 1 and 3 is during unit stoppage (remote controller OFF). It is not necessary to reset the settings by power-off.
Note 2. Settings in the shaded areas are factory settings.
Model System
Capacity code
SW3-2
123456
P250
50 OFF
ON
OFF
P500
Two-refrigerant circuit connection
One-refrigerant circuit connection
One-refrigerant circuit connection
50
OFF
SW2 SW4
12345
123456 12345
ON
OFF
ON
OFF
ON
OFF
*
100
ON
123456 12345
ON
OFF
ON
OFF
* The setting is changed at site under two-refrigerant circuit connection
<Capacity code and function setting>
If the capacity code or the model setting is changed upon replacement of the circuit board, power reset the indoor and outdoor units.